Kingflex Closed Cell Foam Tube Insulation, Using rubber as the main raw material ,no fiber ,non-formaldehyde, non-CFC and other ozone-depleting refrigerant. It can be directly exposed to the air, nor harm for human health .Standard product is black ,there are two major categories: rubber foam insulation sheet and insulation pipe, widely applied in central air-conditioning system water pipelines ,ducts ,hot and cold water pipeline, mine pipe line system, refrigeration system and HVAC system.
● nominal wall thicknesses of 1/4”, 3/8″, 1/2″, 3/4″,1″, 1-1/4”, 1-1/2″ and 2” (6, 9, 13, 19, 25 , 32, 40 and 50mm)
● Standard Length with 6ft (1.83m) or 6.2ft(2m).
Kingflex Technical Data |
|||
Property |
Unit |
Value |
Test Method |
Temperature range |
°C |
(-50 – 110) |
GB/T 17794-1999 |
Density range |
Kg/m3 |
45-65Kg/m3 |
ASTM D1667 |
Water vapor permeability |
Kg/(m.s.pa) |
≤0.91×10 ﹣¹³ |
DIN 52 615 BS 4370 Part 2 1973 |
μ |
- |
≥10000 |
|
Thermal Conductivity |
W/(m.k) |
≤0.030 (-20°C) |
ASTM C 518 |
≤0.032 (0°C) |
|||
≤0.036 (40°C) |
|||
Fire Rating |
- |
Class 0 & Class 1 |
BS 476 Part 6 part 7 |
Flame Spread and Smoke Developed Index |
|
25/50 |
ASTM E 84 |
Oxygen Index |
|
≥36 |
GB/T 2406,ISO4589 |
Water Absorption,%by Volume |
% |
20% |
ASTM C 209 |
Dimension Stability |
|
≤5 |
ASTM C534 |
Fungi resistance |
- |
Good |
ASTM 21 |
Ozone resistance |
Good |
GB/T 7762-1987 |
|
Resistance to U.V. and weather |
Good |
ASTM G23 |