Technical Data Sheet
Kingflex Technical Data |
|||
Property |
Unit |
Value |
Test Method |
Temperature range |
°C |
(-50 - 110) |
GB/T 17794-1999 |
Density range |
Kg/m3 |
45-65Kg/m3 |
ASTM D1667 |
Water vapor permeability |
Kg/(m.s.pa) |
≤0.91×10 ﹣¹³ |
DIN 52 615 BS 4370 Part 2 1973 |
μ |
- |
≥10000 |
|
Thermal Conductivity |
W/(m.k) |
≤0.030 (-20°C) |
ASTM C 518 |
≤0.032 (0°C) |
|||
≤0.036 (40°C) |
|||
Fire Rating |
- |
Class 0 & Class 1 |
BS 476 Part 6 part 7 |
Flame Spread and Smoke Developed Index |
|
25/50 |
ASTM E 84 |
Oxygen Index |
|
≥36 |
GB/T 2406,ISO4589 |
Water Absorption,%by Volume |
% |
20% |
ASTM C 209 |
Dimension Stability |
|
≤5 |
ASTM C534 |
Fungi resistance |
- |
Good |
ASTM 21 |
Ozone resistance |
Good |
GB/T 7762-1987 |
|
Resistance to U.V. and weather |
Good |
ASTM G23 |
1. Closed-cell Structure.
2. Low Heating Conductivity.
3. Low Water Absorption Rate.
4. Good Fireproof and Soundproof Performance.
5. Good Aging Resistance Performance.
6. Simple and Easy Installation.
rubber foam insulation materials application:
Be used to retard heat transmission and control condensation from chilled-water and refrigeration systems. It also efficiently reduces
heat transfer for hot-water plumbing and liquid-heating and dual-temperature piping
It is ideal for applications in:
Ductwork