Kingflex Technical Data |
|||
Property |
Unit |
Value |
Test Method |
Temperature range |
°C |
(-50 - 110) |
GB/T 17794-1999 |
Density range |
Kg/m3 |
45-65Kg/m3 |
ASTM D1667 |
Water vapor permeability |
Kg/(m.s.pa) |
≤0.91×10 ﹣¹³ |
DIN 52 615 BS 4370 Part 2 1973 |
μ |
- |
≥10000 |
|
Thermal Conductivity |
W/(m.k) |
≤0.030 (-20°C) |
ASTM C 518 |
≤0.032 (0°C) |
|||
≤0.036 (40°C) |
|||
Fire Rating |
- |
Class 0 & Class 1 |
BS 476 Part 6 part 7 |
Flame Spread and Smoke Developed Index |
|
25/50 |
ASTM E 84 |
Oxygen Index |
|
≥36 |
GB/T 2406,ISO4589 |
Water Absorption,%by Volume |
% |
20% |
ASTM C 209 |
Dimension Stability |
|
≤5 |
ASTM C534 |
Fungi resistance |
- |
Good |
ASTM 21 |
Ozone resistance |
Good |
GB/T 7762-1987 |
|
Resistance to U.V. and weather |
Good |
ASTM G23 |
1. Air conditioner rubber insulation tube
2. Low conductivity&heat conductivity
3. Closed cell pipe insulation
4. Good fireproof
5.The rubber foam tube has very good stability and can play a good role in preventing fire.
6.The rubber foam tube is flexible, so it is easy to install when it needs to be bent.
The insulation tube is made of NBR and PVC. It doesn't contain fibrous dust, benzaldehyde and
Chlorofluorocarbons. Moreover, it has low conductivity &heat conductivity, good moisture resistence and Fireproof.